Home / Electrical Engineering / Electrical Installations / Cable Voltage Drop (Single Phase)

Formula & Calculator

Cable Voltage Drop (Single Phase)

When current flows through a long cable, some voltage is lost due to the cable's resistance. In a single-phase circuit, the current travels out and back, so the total length is twice the one-way distance. The voltage drop equals two times the length times the current times the resistance per unit length, divided by 1000. For example, a 30 m run carrying 20 A through a cable with 7 ohms per km drops about 8.4 V. Keeping voltage drop low ensures equipment receives the correct voltage.

Electrical Installations Voltage Drop
VORZEP · ELECTRICAL & CABLE ENGINEERING TOOLS

Cable Voltage Drop Calculator — Single Phase

Solve the single-phase voltage drop equation for drop, current, length or cable resistance — with a circuit diagram, cable-size reference tables, and an interactive drop-vs-length graph.

Vd = (2 · L · I · R) / 1000
Solve for
Cable size preset (sets R)
Cable Length (L, one-way) One-way run from source to load. The formula's factor of 2 already accounts for the return conductor, so do not double it yourself.
Load Current (I) The current drawn by the load — use the full-load or design current of the circuit.
A
Cable Resistance (R) Resistance per conductor per unit length. Pick a cable-size preset above, or enter a value from a manufacturer's datasheet.
Voltage Drop (Vd) The voltage lost along the feeder due to conductor resistance: V(load) = V(source) − Vd.
V
Supply Voltage (V₀) Nominal source voltage, used only to express the drop as a percentage — it doesn't feed into Vd itself.
V
VOLTAGE DROP (Vd)
4.7424V
≈ 2.06% of V₀ (230 V)
Within typical 3% guideline
Vd = (2 · L · I · R) / 1000
Step-by-step solution
Result in other units
Sensitivity (+1% change in each input)
Companion Circuit Quantities
Circuit diagram
Source Vs L = 20 m R = 7.41 Ω/km I = 16 A return conductor Load draws I VL Vs level VL level Vd one-way length L (return conductor adds the same length again)

The source delivers Vs; resistance in the go-and-return conductor pair drops Vd along the way, so the load only sees VL = Vs − Vd. The diagram and its labels update with your inputs above.

Voltage drop vs. cable length
Vd for your I and R 3% of V₀ 5% of V₀

Hover or touch the line to read the drop at any length. The amber marker is your calculated operating point; the dashed lines mark the commonly cited 3% and 5% guideline levels for V₀.

How each parameter drives the voltage drop
Vdvoltage drop
=
2go + return
×
L · I · Rlength × current × resistance
÷ 1000

Length ↑

Vd grows directly with distance — doubling the run doubles the drop for the same current and cable size.

Current ↑

Vd is directly proportional to load current — a circuit that draws twice the current sees twice the drop on the same cable.

Cable size ↑

A larger cross-section lowers R and cuts Vd roughly in proportion — upsizing the cable is the standard fix for excess drop over long runs.

Supply voltage

V₀ doesn't change Vd itself, but a higher V₀ makes the same Vd a smaller percentage — this is one reason higher-voltage distribution reduces drop problems.

How to Use This Calculator

The voltage drop equation links four quantities: cable length L, load current I, cable resistance R, and the resulting drop Vd. Pick the one you want solved and fill in the other three.

1. Choose what to solve for

Select Vd, L, I or R under "Solve for". The greyed-out field is the one being calculated.

2. Pick a cable size, or enter R directly

The cable-size preset fills in R for common copper and aluminum conductor sizes. Switch it to "custom" to type your own value from a datasheet.

3. Enter length and current

Length is the one-way run from source to load — the formula's factor of 2 already covers the return conductor. Current is the load's full-load or design current.

4. Set the supply voltage

V₀ doesn't affect Vd itself, but it lets the tool show the drop as a percentage and flag it against the common 3%/5% guidance.

5. Read the result, diagram and graph

The result card shows Vd (or whichever variable you solved for) with a pass/caution/fail badge. The diagram updates with your values, and the graph shows how Vd changes with length.

6. Switch to Advanced for more depth

Advanced mode adds ±1% sensitivity, load-side voltage, power lost in the cable, and the maximum length for 3% and 5% drop.

What This Tool Offers

Built around the standard simplified single-phase voltage drop formula used for quick cable-sizing checks.

Solve any of four variables

Find Vd, length, current or cable resistance — the equation is rearranged for you.

Labeled circuit diagram

A source-to-load schematic showing the go and return conductors, current direction, and where the drop occurs — updates live with your inputs.

Cable resistance reference tables

Standard copper and aluminum conductor resistance by cross-section, ready to plug straight into the calculator.

Interactive drop-vs-length graph

See Vd or %Vd plotted against length, with 3%/5% guideline lines and a hover readout at any distance.

Unit conversion

Length in meters or feet, resistance in Ω/km, Ω/1000ft or Ω/m — convert independently without retyping.

Pass/caution/fail guidance

The result is checked against commonly cited 3% and 5% voltage-drop guidance so you can see at a glance whether a run needs a bigger cable.

What Is Cable Voltage Drop?

Every real conductor has resistance, so as current flows along a cable some voltage is lost before it reaches the load — this is voltage drop. For a single-phase circuit, current must travel out to the load and back through a return conductor, so the total resistance in the circuit is twice the one-way conductor resistance. Excessive voltage drop can cause dim lighting, motors that run hot or stall, and equipment operating outside its rated voltage range, which is why electrical codes and design guides set recommended limits.

Voltage Drop Formula

Vd = (2 · L · I · R) / 1000

Rearranged for the other three variables:

L = (1000 · Vd) / (2 · I · R)
I = (1000 · Vd) / (2 · L · R)
R = (1000 · Vd) / (2 · L · I)

with L in meters and R in ohms per kilometer (Ω/km) per conductor, giving Vd in volts.

Formula Variables

SymbolMeaningTypical unit
VdVoltage dropped along the feedervolts (V)
LOne-way cable length, source to loadm, ft
ILoad (design) currentamps (A)
RResistance per conductor, per unit lengthΩ/km, Ω/1000ft, Ω/m
V₀Nominal supply voltage (for %Vd only)volts (V)

Reference Table — Standard Copper Conductor Resistance

Approximate stranded copper conductor DC resistance at 20°C, by cross-sectional area:

SizeR (Ω/km)R (Ω/1000ft)
1.5 mm²12.13.69
2.5 mm²7.412.26
4 mm²4.611.41
6 mm²3.080.939
10 mm²1.830.558
16 mm²1.150.351
25 mm²0.7270.222
35 mm²0.5240.160
50 mm²0.3870.118
70 mm²0.2680.0817
95 mm²0.1930.0588
120 mm²0.1530.0466
150 mm²0.1240.0378

Reference Table — Standard Aluminum Conductor Resistance

SizeR (Ω/km)R (Ω/1000ft)
16 mm²1.910.582
25 mm²1.200.366
35 mm²0.8680.265
50 mm²0.6410.195
70 mm²0.4430.135
95 mm²0.3200.0975
120 mm²0.2530.0771
150 mm²0.2060.0628

Conversion Table — Units

QuantityConversions
Length1 m = 3.28084 ft · 1 ft = 0.3048 m
Resistance1 Ω/km = 0.3048 Ω/1000ft · 1 Ω/1000ft = 3.28084 Ω/km
Resistance1 Ω/km = 0.001 Ω/m · 1 Ω/m = 1000 Ω/km

Reference Table — Common Voltage Drop Guidance

Widely cited rule-of-thumb limits used in many design guides. Always confirm the specific figure required by the electrical code or standard governing your installation.

Circuit typeCommonly cited limit
Branch / final circuit≈ 3% of nominal voltage
Feeder + branch combined≈ 5% of nominal voltage
Motor starting circuitsOften allowed higher, per equipment manufacturer

Worked Example

Given: L = 20 m, I = 16 A, R = 7.41 Ω/km (2.5 mm² copper), V₀ = 230 V
Vd = (2 × 20 × 16 × 7.41) / 1000
Vd = 4,742.4 / 1000
Vd = 4.74 V (≈ 2.06% of V₀ — within the typical 3% guideline)

Reference & Method Note

This is the simplified single-phase voltage drop formula used for quick sizing checks, based on conductor DC resistance only. It ignores cable reactance and load power factor, which is a reasonable approximation for smaller conductors and typical power-factor loads, but becomes less accurate for large cables or highly reactive loads at higher frequencies — those cases need the fuller Vd = I·L·(R·cosφ + X·sinφ)/1000-style formula with the cable's reactance X and the load's power factor. Resistance values in the reference tables are approximate, room-temperature (20°C) figures; actual conductor resistance rises with operating temperature, so a margin is prudent for circuits that run hot. Always check the voltage-drop limit and method required by the electrical code applicable to your installation.

Frequently Asked Questions

In a single-phase circuit, current flows out to the load through one conductor and back through another. Both conductors add resistance, so the total resistance in the loop is twice the one-way (single-conductor) resistance — that's the 2 in the formula.

L is the one-way distance from source to load. The formula already multiplies by 2 to account for the return conductor, so entering the round-trip distance would double-count it and overstate the drop.

This varies by electrical code and installation type. Many guides commonly cite around 3% for a branch circuit alone and 5% for a feeder plus branch circuit combined, but you should confirm the exact figure required for your jurisdiction and application.

Yes. Conductor resistance rises with temperature, so a cable running hot under load has a higher R — and therefore a higher Vd — than the 20°C reference value used in the tables here.

A three-phase circuit doesn't use a separate full-current return conductor in the same way, so its simplified formula uses a factor of √3 (≈1.732) times L·I·R instead of the single-phase factor of 2. This calculator covers single-phase circuits only.

Calculating...

Variables

Symbol Quantity Unit
V_d Voltage drop V
L Cable length (one-way) m
I Load current A
R Cable resistance (per km) Ω/km

What it means

The voltage drop in a single‑phase cable is given by V_d = (2 × L × I × R) / 1000, where L is the cable length in metres, I is the current in amperes, and R is the resistance of the cable per kilometre (Ω/km). The factor 2 accounts for both the outgoing and return conductors. Voltage drop must be limited to ensure proper operation of equipment (typically <3‑5%). Example: A 100m cable carrying 50A, with a resistance of 0.5Ω/km, has V_d = (2 × 100 × 50 × 0.5) / 1000 = (2 × 100 × 50 × 0.5) / 1000 = (5000) / 1000 = 5V. This is the drop in the cable; the load will see a voltage lower than the supply by 5V.

Worked example

Cable Voltage Drop – Practical Example

Real‑World
Scenario: A 100 m long cable carries 20 A. The cable resistance is 0.5 Ω/km. Calculate the voltage drop for a single‑phase circuit.
ParameterValue
L100 m = 0.1 km
I20 A
R0.5 Ω/km
FormulaVd = (2 × L × I × R) / 1000
1Total resistance: 0.1 km × 0.5 Ω/km = 0.05 Ω (one way)
2Vd = 2 × 20 × 0.05 = 2 V
Final Design Vd = 2 V ✓ Acceptable
Why: Voltage drop depends on cable length, current, and resistance – it should be kept below 5% of nominal voltage.

Common mistakes

Watch for unit mismatches (W vs kW, single- vs three-phase) and remember to include power factor or efficiency where the formula requires it.

Applications

Cable voltage drop (single phase): V_d = (2 × L × I × R)/1000 accounts for the resistance of the two conductors. This ensures that the voltage at the load is within acceptable limits. Engineers use it to size cables for voltage drop, to comply with standards, and to ensure proper operation of equipment.

  • Cable sizing for voltage drop compliance
  • Power distribution design in buildings
  • Transformer and cable loss estimation
  • Motor starting voltage dip analysis
  • Educational understanding of voltage drop