Home / Materials Science / Thermal Properties / Fourier's Law of Conduction

Formula & Calculator

Fourier's Law of Conduction

Fourier's law says heat flows from hot to cold at a rate proportional to the temperature gradient. The heat flux q equals minus the thermal conductivity k times the temperature gradient dT/dx. The negative sign means heat flows down the temperature slope. For example, a copper rod conducts heat much faster than a wooden one because copper has higher thermal conductivity. It is the foundation of heat transfer analysis in buildings, engines, and electronics cooling.

Materials Science Thermal Properties Heat Transfer
VORZEP · HEAT TRANSFER & THERMAL ENGINEERING TOOLS

Fourier's Law Calculator

Solve the classic heat conduction relation q = −k · dT/dx for any of its four unknowns — heat flux, thermal conductivity, temperature difference, or wall thickness — with step-by-step math, a live slab-conduction schematic showing the temperature gradient, and companion thermal metrics including thermal resistance and U-value.

q = − k · ( dT / dx )
Solve for
Heat Flux (q) The rate of heat transfer per unit area, in W/m². The negative sign in Fourier's law indicates heat flows down the temperature gradient; this calculator works with magnitudes. Typical: 1–10 W/m² for high-performance building insulation, 10–100 W/m² for typical walls, 100–1,000 W/m² for windows and poorly insulated surfaces, 1,000–10,000 W/m² for furnace walls and industrial piping, above 10⁵ W/m² for boiling and high-temperature processes.
W/m²
Heat flux must be greater than zero.
= 1.000×10³ W/m² = 1.000 kW/m² · through 1 m²: 1.000 kW
Thermal Conductivity (k) The material's ability to conduct heat, in W/(m·K). Low k means insulation; high k means conductor. Typical: 0.013–0.020 for aerogel, 0.035–0.045 for fibreglass and mineral wool, 0.13–0.18 for softwood, 0.6 for water, 1.0 for window glass, 1.4–3.5 for concrete, 45–60 for carbon steel, 200–240 for aluminium, 385–400 for copper, 5,000+ for graphite and diamond. Gases have very low k because heat is carried by molecular collisions only, with no free electrons.
W/(m·K)
Thermal conductivity must be greater than zero.
= k = 50.00 W/(m·K) · R per mm = 2.000×10⁻⁵ m²·K/W
Temperature Difference (ΔT) The temperature difference across the wall, in kelvin (K) or equivalently in degrees Celsius. Because it is a difference, not an absolute temperature, K and °C give the same number. Typical: 10–20 K for building walls (indoor vs. outdoor), 50–100 K for industrial equipment, 500–1,500 K for furnace walls and kiln linings. The heat flux is directly proportional to ΔT.
K
Temperature difference must be greater than zero.
= 100.0 K = 100.0 °C · 180.0 °F difference
Wall Thickness (Δx) The thickness of the material through which heat conducts, in metres. For composite walls, this is the thickness of each layer in turn. Typical: 1–10 mm for heat exchanger tubes and metal sheets, 10–50 mm for furnace linings, 100–300 mm for building walls with insulation, 500–1,000 mm for industrial kilns. Heat flux is inversely proportional to thickness: doubling the thickness halves the flux.
m
Thickness must be greater than zero.
= 0.100 m = 100.0 mm = 10.00 cm = 3.937 in
HEAT FLUX (q)
1.000e3 W/m²
R = 2.00×10⁻³ m²·K/W · U = 500 W/(m²·K) · Q through 1 m² = 1.000 kW
HIGH FLUX — INDUSTRIAL / FURNACE WALL
q = − k · ( dT / dx )
Step-by-step solution
Heat flux vs. temperature difference
Current k k × 0.25 k × 4
Heat flux vs. thickness
Current ΔT ΔT × 0.5 ΔT × 2
Sensitivity
Companion thermal metrics
Heat conduction through a slab — live schematic
HEAT CONDUCTION THROUGH A SLAB · q = − k · dT/dx HOT SIDE T_h = — COLD SIDE T_c = — SLAB k = — W/(m·K) q TEMPERATURE PROFILE x = 0 x = Δx Δx = 0.100 m q = k · ΔT / Δx = 50 × 100 / 0.100 = 5.000e4 W/m²
Heat flow direction (down the temperature gradient) Linear temperature profile through the slab Thickness Δx determines the temperature gradient
The slope of the temperature profile is dT/dx. A steeper gradient (thinner wall or larger ΔT) drives a higher heat flux.
What Fourier's law really measures
qheat flux
=
−kconductivity
·
dT/dxtemperature gradient

Fourier's law is the heat analogue of Ohm's law

Compare q = −k·dT/dx with Ohm's law J = −σ·dV/dx. Heat flux plays the role of current density, thermal conductivity the role of electrical conductivity, and temperature the role of electric potential. This analogy runs deep: thermal resistance R = Δx/k is exactly like electrical resistance, and composite walls obey series and parallel resistor rules. Heat pipes, thermal interface materials, and heat spreaders are all designed using this analogy, and the same mathematics describes diffusion of mass (Fick's law) and momentum (Newton's law of viscosity).

Flux scales linearly with ΔT and inversely with Δx

Double the temperature difference and the heat flux doubles. Double the wall thickness and the heat flux halves. These two linearities are the everyday design levers: to reduce heat loss through a wall, either reduce the temperature difference (rarely an option) or increase the thickness (adding insulation). To increase heat transfer in a heat exchanger, use a thinner wall or a higher-conductivity material. Combined with the material's k, they give q = k·ΔT/Δx, the working form of Fourier's law for a flat wall.

Composite walls use series resistance

For a wall made of n layers stacked in series (e.g., brick + insulation + plasterboard), the total thermal resistance is the sum of each layer's resistance: R_total = Σ(Δxᵢ/kᵢ). The heat flux is then q = ΔT_total / R_total. This means the least conductive (highest R) layer dominates: adding 50 mm of mineral wool insulation (R ≈ 1.25 m²·K/W) to a solid brick wall (R ≈ 0.15 m²·K/W) increases the total resistance by almost 10×, cutting heat loss by roughly the same factor. This is why modern building standards require thick insulation layers, not thick structural layers.

The U-value summarises a whole wall

Building engineers prefer the U-value (or thermal transmittance), U = 1/R_total, expressed in W/(m²·K). The heat flux through a wall is then simply q = U · ΔT. U-values have intuitive benchmarks: U = 5 W/(m²·K) for single glazing, U = 1.4 for old uninsulated cavity walls, U = 0.3 for typical modern insulated walls, U = 0.15 for high-performance Passivhaus construction, U = 0.05 for vacuum insulation panels. Because U combines all layers — including surface films — into a single number, it is the standard figure quoted in energy codes and retrofit specifications.

How to Use This Calculator

Fourier's law links four quantities: q, k, ΔT and Δx. Pick which one you want the tool to solve, then fill in the other three.

1. Choose what to solve for

Pick q, k, ΔT or Δx from the toggle. The calculator rearranges q = k·ΔT/Δx for whichever quantity you select — this is the magnitude form, dropping the minus sign, with heat flowing from hot to cold by convention.

2. Use realistic presets

Conductivity presets cover insulation, wood, water, glass, steel and copper. Heat-flux presets span 1 W/m² (Passivhaus walls) to 100,000 W/m² (boiling surfaces). Temperature and thickness presets cover building, industrial and furnace ranges.

3. Match units carefully

q is in W/m², k in W/(m·K), ΔT in K (identical to °C for a difference), Δx in metres. All sliders use log scales for q, k and Δx (they span many decades), and a linear scale for ΔT.

4. Read the result and verdict

The result card shows the solved value plus derived metrics — thermal resistance R, U-value, heat rate through 1 m², and a colour-coded verdict classifying the flux from well-insulated to extreme.

5. Check the schematic and charts

The schematic shows the slab with hot and cold faces, heat-flow arrows, and the linear temperature profile plotted below the slab. The chart plots q against ΔT for three conductivity values.

6. Switch to Advanced for depth

Advanced mode adds the q vs. thickness chart, a sensitivity check on a +1 % input change, and companion metrics including thermal resistance, U-value, heat rate, and thermal diffusivity (for transient analysis).

What This Tool Offers

Built around the classic Fourier conduction relation, the foundation of heat transfer, thermal engineering and building physics.

Four-way solving

Solve for heat flux, thermal conductivity, temperature difference, or wall thickness. Every rearrangement is direct algebra from q = k·ΔT/Δx.

Live slab schematic

A slab with hot and cold faces, heat-flow arrows whose thickness scales with flux, and a linear temperature profile plotted below the slab.

Flux-class verdict

Each result is classified from well-insulated (< 10 W/m²) through building, industrial and furnace to extreme (> 10⁵ W/m²), with a coloured badge.

Dual comparison charts

q vs. ΔT for three conductivity values, plus an advanced q vs. Δx chart showing the inverse-proportionality relationship.

Companion thermal metrics

Thermal resistance R = Δx/k, U-value = 1/R, heat rate Q = q·A, thermal diffusivity α = k/(ρ·c_p), and more.

Reference tables

Thermal conductivities by material across five orders of magnitude, a dynamic q lookup grid, and a full variable reference table.

Reference Tables & Conversions

A thermal conductivity unit converter, a dynamic heat-flux lookup grid, and typical conductivity values by material.

Thermal conductivity unit converter

W/(m·K)
W/(cm·K)
kcal/(m·h·K)
Btu/(ft·h·°F)
Btu·in/(ft²·h·°F)
= 50.000 W/(m·K) = 0.5000 W/(cm·K) = 42.99 kcal/(m·h·K) = 28.89 Btu/(ft·h·°F) = 346.7 Btu·in/(ft²·h·°F)

Heat flux lookup — q = k · ΔT / Δx

Rows are temperature difference ΔT, columns are wall thickness Δx. Values in W/m², computed at the current thermal conductivity.

ΔT \ Δx1 mm10 mm100 mm500 mm1 m10 m

Typical Thermal Conductivities

Representative values near room temperature. Thermal conductivity spans over six orders of magnitude across materials.

Materialk (W/(m·K))Note
Aerogel (silica)0.013–0.020Best solid insulator
Vacuum insulation panel0.004–0.008Fumed silica + vacuum
Polyurethane foam0.022–0.028Rigid insulation boards
Mineral wool / fibreglass0.035–0.045Standard building insulation
Cork board0.04–0.05Natural insulation
Air (still, 25 °C)0.026Conduction only — convection absent
Softwood0.13–0.18Along the grain; cross-grain lower
Plywood / particleboard0.13–0.15Structural wood panels
Water (25 °C)0.60Reference liquid
Ethylene glycol0.26Antifreeze coolant
Engine oil (used)0.13Lubricant, coolant
Concrete (dense)1.4–2.5Aggregate-dependent
Concrete (lightweight)0.3–0.8Structural insulating concrete
Window glass (soda-lime)1.0–1.1Standard glazing
Brick (common)0.6–1.0Clay masonry
Soil (dry)0.4–0.8Depends on moisture
Soil (wet)1.5–2.5Moisture increases k
Snow (fresh)0.05–0.25Highly variable
Ice (0 °C)2.2Four times higher than water
Stainless steel 30414–17Lower than carbon steel
Carbon steel (1 % C)43–52Structural and pressure vessel
Cast iron52–58Machine bases, engine blocks
Aluminium (pure)237Heat sinks, cookware
Aluminium alloy 6061167Common structural alloy
Copper (pure)385–401Heat exchangers, wiring
Silver429Best metal conductor
Graphite (in-plane)1,500–2,000Heat spreaders
Diamond (type IIa)2,000–2,200Highest known bulk k
Graphene (monolayer)~5,000Highest measured at nanoscale

Variable Reference

SymbolMeaningTypical rangeUnits
qHeat flux (magnitude)1 – 10⁶W/m²
kThermal conductivity0.005 – 5,000W/(m·K)
ΔTTemperature difference across slab1 – 2,000K (= °C for difference)
ΔxWall thickness10⁻³ – 1m
∇TTemperature gradient ΔT/Δx1 – 10⁶K/m
RThermal resistance per unit area = Δx/k10⁻⁵ – 10m²·K/W
UThermal transmittance = 1/R0.1 – 10⁵W/(m²·K)
QHeat rate through area A = q·A1 – 10⁹W
αThermal diffusivity = k/(ρ·c_p)10⁻⁷ – 10⁻³m²/s

What Does q = −k · (dT/dx) Measure?

Fourier's law describes how heat conducts through a material. It says that the heat flux — the rate of heat flow per unit area — is proportional to the temperature gradient, with the constant of proportionality being the material's thermal conductivity. The negative sign encodes the second law of thermodynamics: heat always flows from hot to cold, never the other way. This single equation underpins the entire field of heat transfer, from the design of building insulation and heat exchangers to the thermal analysis of nuclear reactors, engine components, and biological tissue.

Fourier's Law Formula

The defining differential form is:

q = −k · ( dT / dx )

For a flat slab of finite thickness with steady-state linear temperature profile, this becomes the finite-difference form used by this calculator:

q = −k · ( ΔT / Δx )

Working with magnitudes (the standard engineering convention), the four rearrangements are:

q = k · ΔT / Δx
k = q · Δx / ΔT
ΔT = q · Δx / k
Δx = k · ΔT / q

The heat rate (in watts) through a wall of area A is simply the flux times the area:

Q = q · A = k · A · ΔT / Δx

Two derived quantities are extremely useful in building physics and thermal engineering:

Thermal resistance (per unit area): R = Δx / k    [m²·K/W]
Thermal transmittance (U-value): U = 1 / R = k / Δx    [W/(m²·K)]
Heat flux: q = U · ΔT

For a composite wall of n layers in series, the resistances add: R_total = R₁ + R₂ + … + Rₙ, and U = 1/R_total.

Fourier's Law Variables

SymbolMeaningNotes
qHeat fluxHeat rate per unit area, in W/m²
kThermal conductivityMaterial property, in W/(m·K); higher means better conductor
ΔTTemperature differenceHot-side temperature minus cold-side temperature
ΔxWall thicknessDistance over which the temperature changes
∇TTemperature gradientΔT/Δx; the driving force for conduction
RThermal resistance per unit areaΔx/k; higher R means better insulation
UThermal transmittance1/R; the "U-value" quoted in building energy codes
QHeat rateq·A; total watts flowing through area A

How Each Variable Affects the Heat Flux

Because the relation is linear in k and ΔT and inversely proportional to Δx, each input has a simple and predictable effect. Doubling the thermal conductivity doubles the flux at the same temperature gradient; doubling the temperature difference doubles it again; doubling the wall thickness halves it. In practice the three are coupled: the material sets k, the design sets Δx, and the application sets ΔT. Building designers therefore choose insulation with low k and specify thickness Δx to control the resulting heat loss, whereas heat-exchanger designers choose high-k metals and thin walls to maximise heat transfer between two fluids.

The quantity that summarises a wall's performance is the U-value, U = k/Δx. Two walls of different thickness and different conductivity can have the same U-value — the same heat loss per unit area per degree of temperature difference. This is why modern building codes are written in U-values, not in material thicknesses: a 250 mm wall of k = 0.04 insulation has the same U as a 100 mm wall of k = 0.016 aerogel. Lower U-values mean better insulation, and the Passivhaus standard pushes U down to 0.15 W/(m²·K) or lower — roughly one-tenth the U of an uninsulated cavity wall.

Fourier's Law Calculation Examples

Given: k = 50 W/(m·K), ΔT = 100 K, Δx = 0.1 m — solve for q
q = 50 × 100 / 0.1 = 50,000 W/m²
Given: q = 50,000 W/m², ΔT = 100 K, Δx = 0.1 m — solve for k
k = 50,000 × 0.1 / 100 = 50 W/(m·K)
Given: q = 50,000 W/m², k = 50 W/(m·K), Δx = 0.1 m — solve for ΔT
ΔT = 50,000 × 0.1 / 50 = 100 K
Given: q = 50,000 W/m², k = 50 W/(m·K), ΔT = 100 K — solve for Δx
Δx = 50 × 100 / 50,000 = 0.1 m = 100 mm
Building wall example: k = 0.04 W/(m·K), ΔT = 20 K, Δx = 0.1 m
q = 0.04 × 20 / 0.1 = 8 W/m² — well insulated
Furnace wall example: k = 1.2 W/(m·K), ΔT = 800 K, Δx = 0.2 m
q = 1.2 × 800 / 0.2 = 4,800 W/m² — industrial-scale flux

Frequently Asked Questions

The negative sign encodes the direction of heat flow: heat always moves from hot to cold, never the reverse. In one dimension, if temperature decreases in the +x direction, then dT/dx is negative, and the minus sign makes q positive, i.e. flowing in the +x direction. If temperature increases in the +x direction, dT/dx is positive, and the minus sign makes q negative, flowing in the −x direction. Either way, the heat flux vector points down the temperature gradient, from higher temperature to lower temperature. This is a statement of the second law of thermodynamics — heat conduction is an irreversible process that spontaneously moves energy from hot to cold, increasing entropy. This calculator works with magnitudes, following standard engineering practice.

The U-value (thermal transmittance) is U = k/Δx for a simple wall, or U = 1/R_total for a composite one. It measures heat loss per unit area per kelvin of temperature difference, so lower is better. Benchmarks: single-glazed windows U ≈ 5–6 W/(m²·K); old uninsulated cavity walls U ≈ 1.5; standard modern insulated walls U ≈ 0.3 (UK Part L and US IECC requirements); Passivhaus walls U ≈ 0.15; vacuum insulation panels U ≈ 0.005–0.008. To convert a U-value to heat flux, multiply by ΔT: a wall with U = 0.3 exposed to a 20 K indoor-outdoor temperature difference loses 6 W/m². Multiply by wall area to get total watts.

In steady state, energy conservation requires that the heat flux be the same at every cross-section of the wall — no heat can accumulate anywhere. Fourier's law says q = −k·dT/dx. If k is constant through the wall and q is constant, then dT/dx must also be constant, which means the temperature varies linearly with position. This is the reason the temperature profile through a homogeneous slab is a straight line. In a composite wall (e.g. brick + insulation + plaster), each layer is a straight line with a different slope: the high-k layer has a shallow slope and the low-k layer has a steep slope. The overall profile is piecewise linear, with the flatter layer containing less temperature drop and the steeper layer containing more.

Yes, but the change is modest for most solids over moderate temperature ranges — typically a few percent per 100 K — so using a single room-temperature k value is acceptable for design work. Gases rise with temperature (air's k goes from 0.024 at 300 K to 0.045 at 600 K), while most metals fall slightly (copper's k drops from 401 at 300 K to 380 at 600 K). The exception is very-high-temperature applications where radiation becomes a significant heat-transfer mechanism inside porous materials (insulations above 500 °C), and where k must be treated as an effective value including radiation across pores. For precise work, use k(T) from a materials database and integrate.

For layers stacked in series — the usual case for a wall with multiple materials — the thermal resistances add: R_total = R₁ + R₂ + R₃ + …, and the U-value is U = 1/R_total. The heat flux is the same through every layer, so q = ΔT_total/R_total. For layers arranged in parallel — such as insulation between timber studs, where the studs are much more conductive than the insulated cavities — the U-values add weighted by area fraction: U_parallel = f₁·U₁ + f₂·U₂. In practice, walls often have both: solid layers in series, and within one layer, insulation and studs in parallel. The combined U is computed by summing resistances for the series parts and averaging by area fraction for the parallel parts.

Fourier's law is the constitutive equation that describes heat flux from a temperature gradient, at any instant. Combining it with energy conservation gives the transient heat conduction equation: ∂T/∂t = α·∇²T, where α = k/(ρ·c_p) is the thermal diffusivity. This partial differential equation describes how temperature evolves over time — during warm-up, cool-down, or a changing boundary condition. Fourier's law alone only describes the steady-state case where the temperature profile is fixed and heat flux is constant. For transient problems, engineers solve the heat equation analytically (for simple geometries) or numerically by finite differences or finite elements. The thermal diffusivity α controls how quickly temperature changes propagate: high-α materials like copper (α ≈ 1.1×10⁻⁴ m²/s) equilibrate in milliseconds, while low-α materials like wood (α ≈ 10⁻⁷ m²/s) take hours.

Conduction is heat transfer through a material by molecular vibrations and (in metals) free-electron motion — it requires no bulk motion of the material, and it is what Fourier's law describes. Convection is heat transfer from a surface to a moving fluid (or vice versa), governed by Newton's law of cooling q = h·ΔT, where h is the convective heat-transfer coefficient (typically 5–25 W/(m²·K) for natural convection in air, up to 1,000 for forced water convection). Radiation is heat transfer by electromagnetic waves, governed by the Stefan–Boltzmann law q = ε·σ·(T₁⁴ − T₂⁴), and it dominates at high temperatures. Real heat-transfer problems usually combine all three: for example, a hot pipe loses heat by conduction through its insulation, by convection to the surrounding air, and by radiation to nearby surfaces. This calculator handles the conduction part only.

Calculating...

Variables

Symbol Quantity Unit
q Heat flux W/m²
k Thermal conductivity W/m·K
dT/dx Temperature gradient K/m

What it means

Fourier’s law of heat conduction states that the heat flux (q) – the rate of heat transfer per unit area – is proportional to the negative temperature gradient (dT/dx) in the direction of heat flow. The proportionality constant is the material’s thermal conductivity (k). The negative sign indicates that heat flows from hotter to colder regions. This law is fundamental for analysing steady‑state conduction in solids. It is used to design thermal insulation, heat exchangers, electronic cooling systems, and building envelopes. In combination with the energy balance, it leads to the heat equation. Engineers use Fourier’s law to calculate heat losses, determine insulation thickness, and predict temperature distributions. Materials with high k (e.g., metals) are good conductors; those with low k (e.g., foams) are insulators. Understanding this law is essential for thermal management in engineering and for energy efficiency.

Worked example

Fourier's Law of Conduction – Two Examples

Real‑World
Scenario: A building wall has thermal conductivity k = 0.04 W/m·K (insulation material). The temperature gradient through the wall is −20 K/m. The energy engineer needs to calculate the heat flux to determine the insulation performance and size the heating system accordingly.
ParameterValue
k0.04 W/m·K
dT/dx−20 K/m
1q = −0.04 × (−20) = 0.8 W/m²
Result 0.8 W/m² ✓ Low heat loss
Scenario: A copper heat sink (k = 401 W/m·K) has a temperature gradient of −100 K/m. The thermal engineer calculates the heat flux to verify the heat sink's ability to dissipate heat from an electronic component without exceeding the maximum junction temperature.
ParameterValue
k401 W/m·K
dT/dx−100 K/m
1q = −401 × (−100) = 40,100 W/m²
Result 40,100 W/m² ✓ High heat flux
Materials insight: Fourier's law states heat flux is proportional to the temperature gradient. Materials with high thermal conductivity (copper, aluminium) are used for heat dissipation; low conductivity materials (insulation) are used for thermal barriers.

Common mistakes

  • Negative sign: Heat flows from hot to cold – the negative sign indicates that the flux is in the direction of decreasing temperature.
  • Thermal conductivity k: Material‑dependent and often temperature‑dependent – use the value at the mean temperature.
  • Temperature gradient dT/dx: The rate of change of temperature with distance – in K/m (or °C/m).
  • Units: q in W/m², k in W/(m·K), gradient in K/m – ensure consistency.
  • Steady‑state: This law applies to steady‑state conduction (no accumulation). For transient, use the heat equation.

Applications

Fourier's law of conduction, q = −k·(dT/dx), describes the rate of heat transfer by conduction through a material, where q is the heat flux (W/m²), k is the thermal conductivity, and dT/dx is the temperature gradient. This law is fundamental to thermal design in electronics, buildings, and industrial processes. Mechanical engineers use it to design heat sinks, insulators, and heat exchangers. In building engineering, it guides insulation thickness for energy efficiency. In materials science, it helps characterise the thermal properties of new materials. By applying Fourier's law, engineers can predict temperature distributions, size cooling systems, and optimise thermal management to ensure safety and performance in electronic devices, engines, and energy systems.

  • Thermal design of electronics (heat sinks, thermal interface materials)
  • Insulation design for buildings, pipes, and cryogenic systems
  • Heat exchanger performance analysis and sizing
  • Thermal management in automotive and aerospace systems
  • Materials characterisation and thermal conductivity measurement